Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1.2; Section 203/203A: It is not clear from the P1 Array Plan where the Section 203 (purlin splice allowed) can occur, and where the Section 203A (purlin splice not allowed) can occur. Please clarify on the plan or on Section 203.
2. Structural Calculations: Please provide the calculations for the purlin design.
3. General: Please provide the Special Inspection Certificate with completed Parts A and B for High Strength Bolting and Caisson inspections.
4. General: Please provide written responses to all review comments.
02/14/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved