Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM00194
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/22/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
03/06/2019 | ERIC NEWCOMB | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide load calculations for the existing switchgear or justify de-rating the main service disconnect by 200 amps. The concern is will the 1400 amp fuses handle the load in the instance the PV system is not generating electricity or off line for any reason. Ref; 2017 NEC art 220.40, 230.79, 2018 IBC sec 107.2.1 |
03/06/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/21/2019 | DAVID RIVERA | ZONING | REVIEW | Approved | |
03/28/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/09/2019 | AMARTIN1 | OUT TO CUSTOMER | Completed |