Permit Number: T19CM00134
Parcel: 110030010

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T19CM00134
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2019 ANDREW CONNOR ZONING REVIEW Approved
01/08/2019 ACONNOR1 LANDFILL REVIEW Passed
01/08/2019 ACONNOR1 ENGINEERING REVIEW Passed
01/08/2019 ANDREW CONNOR NPPO REVIEW Passed
01/08/2019 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T19CM00134
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans. Update all highlighted dates on sheets C1.0, S1.1, S1.2, S1.3, G1.0, PM1 and E1.0.

SECTIONS - DETAILS:

1. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground, R317.1 item 5. Update the 4" notation at detail 1 & 2 /S1.1.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

FLOOR PLANS:

1. Show compliance with R310 providing egress from bedrooms with minimum net clear opening width of 20". The 8040XOX should comply because the 3040SH does not provide the minimum 36" clear opening height.

ELECTRICAL PLANS:

1. Show overcurrent protection not exceeding the allowable conductor ampacity, E3705.5. Revise the breaker or wire size shown for circuit #12/14.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review