Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM00076
Parcel: 11707177B

Address:
133 E 17TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T19CM00076
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2019 NICHOLAS ROSS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Nick Ross
Lead Planner

PROJECT:
T19CM00076
133 E. 17th St
New SFR

TRANSMITTAL: January 4, 2019
COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

This site is located in the HR-3 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The proposed setback on the north property line is 4'0". The proposed setback on the east property line is 3'9".

The minimum setback to a side street property line is ten (10) feet (UDC Section 6.4.5.C.1.b). The proposed setback is 1'6".

Historic Review is required.
01/04/2019 NROSS1 ENGINEERING REVIEW Passed
01/04/2019 NROSS1 NPPO REVIEW Passed
06/06/2019 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Needs Review