Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM00074
Parcel: 13013042A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T19CM00074
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/12/2019 IMONSHI1 ZONING REVIEW Reqs Change FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: T19CM00074 - New Building Addition - General Manufacturing
Building Plan Review (1st Review of Revision) Floor Systems of Arizona / Relate to DP19-0004
3501 E Golf Links / I-1 Zoning

TRANSMITTAL DATE: November 12th, 2019

DUE DATE: November 26th, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Square footage for the flooring systems building shown on the building plan (9,411 sf) doesn't match the square footage on the occupancy load / existing building square footage note or the sf shown on the Development package (9,260 sf). The square footage of the addition is not consistent with that of the one shown on the DP, however since its less than the one shown on the DP it is acceptable.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP.

3. COMMENT: Once the plans have been reviewed and approved by PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact Iman Monshizadeh at (520) 837-4082 or by email Iman.Monshizadeh@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
11/18/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the plumbing fixture calculations on sheet TS.1 to reflect the changes made to the number of provided plumbing fixtures. Reference: Section 2901.2, IBC 2018.
2. Provide the required service sink and drinking fountains. Reference: Section 2901.2, IBC 2018.
3. If a point of use water dispenser is substituting for the required drinking fountains, specify the appliance and show the water supply location. Reference: Section 107.2.1, IBC 2018 and Section 410.3, IPC 2018.
4. Detail3/P.2 shows the proposed water heater sitting on the second floor but the second floor plumbing plan, 2/P.1, shows the temperature and pressure relief pipe located above the seco0nd floor ceiling. Revise the design to prevent the relief pipe from being trapped and allow it to flow by gravity to the discharge point. Reference: Section 504.6, IPC 2018.
5. A ¾" pipe has a maximum allowable pipe length of 6-inches from the hot water source to the lavatory in a public restroom. Reference: Section C404.5.1, IECC 2018.
11/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the energy code calculations (COMcheck) to reflect the changes made to the exterior walls of the building addition. Reference: Section C502.1, IECC 2018.
2. Contrary to the detail titles on sheet A.6, the new 6D walls are bearing. Coordinate the wall changes with the structural design. Reference: Section 107.2.1, IBC 2018.
11/27/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/09/2019 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/16/2019 KROBLES1 OUT TO CUSTOMER Completed