Permit Number: T19CM00074
Parcel: 13013042A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM00074
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 2; Sheet EP.1; Second Floor Exiting Plan: The travel distance indicates 85' travel distance to the exit door (previously indicated 111' to the bottom of the stair). Please verify the distance to the exit door, and indicate on the drawing the exit access travel distance requirement in Table 1017.2 is met.
2. General: Please provide a written response to this review comment.
08/19/2019 AMARTIN1 ENGINEERING REVIEW Reqs Change