Permit Number: T19CM00074
Parcel: 13013042A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM00074
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/07/2019 ROBERT SHERRY WATER REVIEW Completed
08/07/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/08/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TS.1; Project Code Check: Since the occupant load is greater than 15, the Code requires two restrooms (men's and women's or both unisex) and two lavatories. Please indicate this in the required fixtures.
2. Sheet EP.1; Second Floor Exiting Plan: The travel distance indicates 111' to the bottom of the stair. This distance must be measured to the exit. Please revise.
3. General: Please provide written responses to all review comments.
08/14/2019 PMARTIN1 ENGINEERING REVIEW Needs Review