Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM00074
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2019 | QJONES1 | ENGINEERING | REVIEW | Needs Review | |
| 07/19/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Replot sheet P.1 so that the note is not covered by the Bramic Design Group Logo. [Initial comment Verify the materials that have been used for the existing building sewer piping that will be covered by the addition are suitable for use under the addition. Reference: Section 702.2, IPC 2018.] 2. The rim elevation and the FFE have not been provided. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.] |
| 07/19/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Coordinate the maximum U-value for the fenestration used in the COMcheck with the table of U-values on sheet TD1. [Initial comment: Provide sufficient detail on the drawings to compare the energy compliance of the building envelope (COMcheck) with the building components shown on the drawing. Show the maximum U-value and the maximum SHGF values for the fenestration components. Reference: Section C103.2, IECC 2018.] |
| 07/19/2019 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Site plan not provided. [Initial comment Revise the site plan to show the location of the new ¾" water meter. Reference: Section 107.2.1, IBC 2018.] |
| 07/25/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 5; Means of egress: Illustrate on the plans the means of egress and egress travel distances for the entire building including new addition . IBC Chap.10 , IBC 107.2.1. No travel distances are indicated. 2. Previous Comment 7; Sheet TS.1 - Project Code Analysis - provide the minimum number of required plumbing fixtures with code analysis . IBC 107.2.1 , IBC 2902. Please review the required plumbing fixtures per the IBC Table 2902.1. Two water closets and two lavatories are required. In addition, no single point of use water dispenser was located on Sheet A.1 or Sheet P.3. 3. |
| 08/06/2019 | PCAMARE1 | ZONING | REVIEW | Approved |