Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM00022
Parcel: 11904442A

Address:
3508 S 8TH AV

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T19CM00022
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL PLAN REVIEW COMMENTS T19CM00022
Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Line Diagrams.
(a) Indicate the AIC rating of the service equipment.
(b) One diagram (E5.00) calls out 3-350 mcm and 1-#2 cu for the riser conductors.
(c) The other diagram (E6.00) calls out 3-350 mcm and 1#1 cu. Are these Grounds or neutrals? Please clarify.
(d) Why are there 2 separate grounding electrode systems shown on E5.00? If this is the desired design of the grounding system they should be common per 250.58 2017 NEC.
(e) Please indicate the total number of conductors and sizes for note 5 on plan sheet E1.00.
(f) Be more specific as to how the parallel feeders are distributed to all the units. Or include a complete line diagram for the parallel feeders.
(g) Indicate whether the existing Triplex in aluminum or copper.
(h) Justify that the outside taps are in accordance with NEC art 240.
REF; 2017 NEC, 2018 IBC sec 107.2.1