Permit Number: T19CM00018
Parcel: 137084560

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM00018
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The line diagrams have a note stating, "CONNECTION VIA LINE SIDE TAP TO EXISTING FEEDERS", however the photograph (E5-4) showing the location of the proposed tap shows existing bus with no "EXISTING FEEDERS" terminated. Unless the bus is marked "TAP" by the manufacturer at this location on the bus, a field evaluation by an NRTL will be necessary to maintain the listing of the equipment.
REf; 2011 NEC 110.3C, UL GUIDE FOR ELECTRICAL EQUIPMENT section 'WEVZ'

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2019 TWEIDEM1 OUT TO CUSTOMER Completed
06/17/2019 TWEIDEM1 REJECT SHELF Completed
06/05/2019 TWEIDEM1 APPROVAL SHELF Completed