Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM00018
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/05/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The line diagrams have a note stating, "CONNECTION VIA LINE SIDE TAP TO EXISTING FEEDERS", however the photograph (E5-4) showing the location of the proposed tap shows existing bus with no "EXISTING FEEDERS" terminated. Unless the bus is marked "TAP" by the manufacturer at this location on the bus, a field evaluation by an NRTL will be necessary to maintain the listing of the equipment. REf; 2011 NEC 110.3C, UL GUIDE FOR ELECTRICAL EQUIPMENT section 'WEVZ' |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/17/2019 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
06/17/2019 | TWEIDEM1 | REJECT SHELF | Completed |
06/05/2019 | TWEIDEM1 | APPROVAL SHELF | Completed |