Permit Number: T19CM00018
Parcel: 137084560

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM00018
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Plan sheet E4.1 still shows a load side tap utilizing a J-Box. Please revise.
2. Unless the bus is identified as "TAP" by the manufacturer at the point of the PV interconnection a field evaluation by a NRTL will be required to evaluate the service equipment in order to maintain the listing.. Please provide for this on the plans.
REf; 2011 NEC 110.3C, UL GUIDE FOR ELECTRICAL EQUIPMENT section 'WEVZ'
05/23/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/23/2019 TWEIDEM1 APPROVAL SHELF Completed