Permit Number - T19CM00018
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Plan sheet E4.1 still shows a load side tap utilizing a J-Box. Please revise. 2. Unless the bus is identified as "TAP" by the manufacturer at the point of the PV interconnection a field evaluation by a NRTL will be required to evaluate the service equipment in order to maintain the listing.. Please provide for this on the plans. REf; 2011 NEC 110.3C, UL GUIDE FOR ELECTRICAL EQUIPMENT section 'WEVZ' |
| 05/23/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |