Permit Number: T19CM00010
Parcel: 13405119H

Address:
9401 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM00010
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The vent for the new combination waste and vent system shall rise vertically to at least 6" above the flood rims of the floor drains it protects prior to running horizontally. Reference: Sections 905.4 and 915.2.3, IPC 2018.
01/29/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum height of 3/32-inch (this does not apply to the refrigeration shop drawings). Reference: Section 107.2.1, IBC 2018.
2. Show that the new dairy island cases comply with the minimum energy requirements of Section 403.10, IECC 2018.
01/29/2019 ROBERT SHERRY WATER REVIEW Completed
02/11/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The City of Tucson has adopted the 2017 NEC Jan 1 2019. Please reference this, instead of 2011.
2. Show the location of the 112.5 KVA transformer that feeds the new panel A on the plans. If the transformer is more than 25' from the panel, provide a fused disconnect at the transformer location for protection of the secondary feeders. NEC 240.15, 240.21.
Ref; 2018 IBC sec 107.2.1, 2017 NEC
02/14/2019 LOREN MAKUS ENGINEERING REVIEW Passed
02/19/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T19CM00010 - Food Servicer Use - Fry's Food Store (Tenant Improvement)
Building Plan Review (1st Review) - Related to DP19-0021
901 E. 22nd Street - C-1 Zoning

TRANSMITTAL DATE: February 19, 2020

DUE DATE: February 19, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the tenant improvement plans for the interior remodel. While zoning has not concerns related to the interior remodel of the building the proposed striping of the parking lot requires approval of a Development Package.

A related application, DP19-0021 has been submitted for review for the proposed re-striping for a pick-up area. The sheets in the TI set related to the re-striping may be removed from the building plans in order to have the T.I. approved by zoning.


2. If the decision is made to remove the re-striping sheets from the T.I. set, zoning can approve the T.I. application and stamp the plans over the counter.


3. If the re-striping plans are to remain in the T.I. set assure that any DP comments are addressed and that the revised DP sheets are included in the T.I. set before re-submittal. Keep in mind that the DP must be approved before the T.I. is approved by Zoning.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: as noted above
03/07/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved 1. Sheet G0.1; Project Codes: After January 1, 2019, all international codes should follow the 2018 editions, and the 2017 NEC. Please revise and verify these drawings meet the requirements of the updated codes.
2. Sheet G0.1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise.
3. Sheet G0.1 (Project Description); Sheet F1 (Fixture Plan): The Project Description indicates a new 484 SF "Pick-Up" room, while the Fixture Plan indicates 527 SF. Please coordinate.
4. Sheet F1.1; Fixture Plan 1: Please identify the vertical grid lines on this plan.
5. Sheet AD1.1; Demolition Plan 2: Please identify the vertical grid lines on this plan.
6. Sheet A4.1; Plans 1, 2, 3, and 4: The plan titles indicate demolition plans. Please revise.
7. Sheet A4.1; Floor Plan Legend: The new wall references Sheet A5.1 for partition types. Please add Sheet A4.1 to that reference.
8. Sheet A4.1; Floor Plan Legend: Please add a symbol and note to reference the door schedule on Sheet A5.1.
9. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov