Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19BU00626
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0: Please provide a new sheet that correctly identifies the three buildings to be demolished. The current sheet indicates one building to be demolished and two buildings to remain. For each building to be demolished, include the address, building square footage, building construction type, and building occupancy classification. 2. Sheet A1.0: The Code Review Checklist was useful for the original development package, but should be removed on the new sheet. 3. General: Please provide a Confirmation Of Notice Of Demolition form. This form may be found on our website under 'All Application Forms'. 4. General: Please contact Pima County at 520-740-3340 to obtain a form for a demolition/renovation asbestos NESHAP exemption. 5. General: Please provide written responses to all review comments. |
| 01/08/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/19/2019 | ANY | ENGINEERING | REVIEW | Active | |
| 12/19/2019 | ANY | OIP | REVIEW | Active | |
| 12/19/2019 | ANY | FIRE | REVIEW | Active | |
| 12/19/2019 | ANY | ZONING | REVIEW | Active |