Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19BU00497
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/17/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code for the pool luminaires. Include a complete lumen calc for the premises. 2. Provide GFI protection for the pool pumps as required per NEC art 230.21C. 3. Provide GFI protection for the pool luminaires as required per NEC art 680.22. Ref; 2017 NEC, 2018 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |
| 10/30/2019 | PMARTIN1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 10/30/2019 | PMARTIN1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review |