Permit Number - T19BU00496
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/03/2020 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | Below are comments on the authorized repair resubmittal for COT ID# 398 at 2229 North Stone Avenue (T19BU00496 R). Sheet 2 of 2 1. In revised 6th paragraph of Scope of Work, refer only to installation of the one replacement lower backrail (upper backrail already covered in 4th paragraph) and add the length of the replacement lower backrail. 2. In revised South Sign Face Rear Elevation, add the length of the existing upper wood backrail, consistent with that listed in the 1st paragraph of Scope of Work. 3. In revised South Sign Face Rear Elevation & Poster Panel Side View, the replacement wood stringer thickness is shown as 2-inch, while in the 8th paragraph of Scope of Work and Backrail & Stringer Mounting Detail it shown as 3-inch thick; please resolve this conflict and clarify if the stringer is to be centered or offset. 4. In revised South Sign Face Rear Elevation, depict and call out the full-length run of conduit that is attached to the upper wood backrail. 5. In revised Light Mounting Detail, indicate rigid conduit to be detached from upper wood backrail and reattached (rather than to remain). |