Permit Number: T19BU00390
Parcel: 99999999B

Address:
1299 E BENSON HY

Review Status: Active

Review Details: BILLBOARD - BLDG30days

Permit Number - T19BU00390
Review Name: BILLBOARD - BLDG30days
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/26/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/16/2019 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Below are comments on the electrical repair submittal for COT ID# 5 at 1299 East Benson Highway (T19BU00190).

Prior to a more detailed review of the plan, the two comments below need to be addressed as to whether or not the proposed work more generally complies with the terms of the Stipulation

Sheet 2 of 2

1. From the point of electrical service origination through junction box that feeds the individual light fixtures, numerous replacement parts are not like as to location, dimensions, and other characteristics; please provide any additio0nal information for consideration as to how these proposed changes would comply with the Stipulation, particularly as to the electrical service line.

2. In the 6th paragraph of Scope of Work, proposed installation of a new service line and associated parts are stated to be covered under a different activity number (T19CM00903); provide a specific reference to where in the electrical plan sheets for that activity number the proposed work is covered and further explain how proposed work on a billboard under a permit for construction unrelated to the billboard is permitted by the Stipulation.


A review of the submitted electrical plans under that activity number shows no such service line to the subject billboard;


Below are comments on the electrical repair submittal for COT ID# 5 at 1299 East Benson Highway (T19BU00190).

Prior to a more detailed review of the plan, the two comments below need to be addressed as to whether or not the proposed work more generally complies with the terms of the Stipulation

Sheet 2 of 2

1. From the point of electrical service origination through junction box that feeds the individual light fixtures, numerous replacement parts are not like as to location, dimensions, and other characteristics; please provide any additio0nal information for consideration as to how these proposed changes would comply with the Stipulation, particularly as to the electrical service line.

2. In the 6th paragraph of Scope of Work, proposed installation of a new service line and associated parts are stated to be covered under a different activity number (T19CM00903); provide a specific reference to where in the electrical plan sheets for that activity number the proposed work is covered and further explain how proposed work on a billboard under a permit for construction unrelated to the billboard is permitted by the Stipulation.


A review of the submitted electrical plans under that activity number shows no such service line to the subject billboard;
Below are comments on the electrical repair submittal for COT ID# 5 at 1299 East Benson Highway (T19BU00190).

Prior to a more detailed review of the plan, the two comments below need to be addressed as to whether or not the proposed work more generally complies with the terms of the Stipulation

Sheet 2 of 2
1. From the point of electrical service origination through junction box that feeds the individual light fixtures, numerous replacement parts are not like as to location, dimensions, and other characteristics; please provide any additio0nal information for consideration as to how these proposed changes would comply with the Stipulation, particularly as to the electrical service line.
2. In the 6th paragraph of Scope of Work, proposed installation of a new service line and associated parts are stated to be covered under a different activity number (T19CM00903); provide a specific reference to where in the electrical plan sheets for that activity number the proposed work is covered and further explain how proposed work on a billboard under a permit for construction unrelated to the billboard is permitted by the Stipulation.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/19/2019 ANY REJECT SHELF RECEIVED