Permit Number: T19BU00365
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T19BU00365
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2020 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Below are comments on the authorized repair second resubmittal for COT ID# 257 at 1315 East Valencia Road (T19BU00365 R2). Notell field observations that form the basis of comments below were performed without physical contact with the subject billboard or otherwise trespassing on Clear Channel property.



Sheet 1 of 4

None

Sheet 2 of 4

1. In 10th paragraphs of Scope of Work-East Face, revise apron height as necessary (see Comment #1 below for Sheet 3 of 4)

Sheet 3 of 4

1. Per Comment #5 on prior resubmittal, in Poster Panel Side View (East Face ), revise vertical dimension of apron to reflect existing dimension below face (2’0” is shown while existing is plainly well under 2’0”, scaling to 1’3”; the finished installation needs to reflect this like configuration, whether or not the portion of the apron now behind the face panel is eliminated).

Sheet 4 of 4

None

Final Status

Task End Date Reviewer's Name Type of Review Description
03/10/2022 KROBLES1 OUT TO CUSTOMER Completed