Permit Number: T19BU00240
Parcel: 99999999A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19BU00240
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a complete grounding detail. Include all pool equipment, accessories, ladders, equipotential bonding, etc.
2. Provide pool luminaires lamp color temperature, not to exceed 3500K per outdoor lighting code.
3. Provide for ground fault protection per NEC art 680.21, 680.23A(3).
Ref; 2017 NEC, 2018 IBC 107.2.1, Tucson/Pima County Outdoor Lighting Code.
05/22/2019 MCASTRO2 ENGINEERING REVIEW Passed
05/22/2019 MCASTRO2 ZONING REVIEW Approved
06/10/2019 AMARTIN1 FIRE REVIEW Needs Review
06/10/2019 AMARTIN1 BUILDING-COMMERCIAL REVIEW Needs Review
06/10/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed