Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19BU00240
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/22/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide a complete grounding detail. Include all pool equipment, accessories, ladders, equipotential bonding, etc. 2. Provide pool luminaires lamp color temperature, not to exceed 3500K per outdoor lighting code. 3. Provide for ground fault protection per NEC art 680.21, 680.23A(3). Ref; 2017 NEC, 2018 IBC 107.2.1, Tucson/Pima County Outdoor Lighting Code. |
| 05/22/2019 | MCASTRO2 | ENGINEERING | REVIEW | Passed | |
| 05/22/2019 | MCASTRO2 | ZONING | REVIEW | Approved | |
| 06/10/2019 | AMARTIN1 | FIRE | REVIEW | Needs Review | |
| 06/10/2019 | AMARTIN1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/10/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed |