Permit Number: T19BU00240
Parcel: 99999999A

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T19BU00240
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete electrical power and lighting plans, sealed by a registrant registered in the state of Arizona. See City of Tucson Electrical Commercial Plan Submittal Requirements can be downloaded at www.tucsonaz.gov/pdsd; Permit Review; Commercial Permits; Commercial Plan Review. Include branch circuit designations, panel schedules, Indicate clearly all light fixture symbols and their associated inverter.
Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code for the new pool lighting including any area lighting.
Ref; 2018 IBC sec. 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code
05/09/2019 MARTIN BROWN FIRE REVIEW Reqs Change Drawings show locks, bolts and latches. Occupant Load is 307. Doors require panic hardware. IFC 2018, 1010.1.9.4 Locks and Latches. & 1010.1.10
05/09/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/22/2019 AMARTIN1 MECHANICAL-COMMERCIAL REVIEW Needs Review
05/22/2019 AMARTIN1 BUILDING-COMMERCIAL REVIEW Needs Review
05/22/2019 AMARTIN1 ENGINEERING REVIEW Needs Review
05/22/2019 AMARTIN1 ZONING REVIEW Needs Review