Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD - BLDG/SIGN10days
Permit Number - T19BU00229
Review Name: BILLBOARD - BLDG/SIGN10days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/15/2019 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | Below are comments on the billboard removal (demolition) submittal for COT ID# 600 at 4711 East Valencia Road (T19BU00229). Sheet 1 of 1 1. In Billboard Note #3, correct the APN (to conform with correct number shown on site plan with aerial photograph underlay). 2. In the 1st paragraph of Notes below Legal Description, please clarify if the utility pole that is near the north Valencia Road right-of-way line, and that appears to have been installed only to serve this billboard, is customer-owned or utility-owned ; if customer-owned or no longer to be otherwise used by the utility company, specify removal. |
| 05/15/2019 | HEATHER THRALL | SIGNS | SIGN CODE REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/24/2019 | PMARTIN1 | OUT TO CUSTOMER | Completed |