Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19BU00162
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T19BU00162
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/29/2019 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Reqs Change Below are BRC comments on the authorized repair submittal for COT ID# 542 at 5371 North Casa Grande Highway (T19BU00162)

Sheet 1 of 3

1. In the 2nd sentence of Billboard Note #8, clarify the language to better state removal within 11 years after the Judgment date and specify the date certain in parentheses at the end of the sentence (November 16, 2020).

Sheet 2 of 3
1. At end of sentence of 3rd t paragraph in 1st boxed note below Scope of Work, add date certain of removal in parentheses (November 16, 2020).

2. Revise title of “Partial Site Plan” to “Partial Vicinity Map”.

Sheet 3 of 3
1. Add manufacturer’s literature sheet with dimensional detail for the upper and lower safety cable mounting brackets (Page 2 of 3M DBI-SALA Lad-Saf Technical Data Sheet (Release 1, February 2018) or equivalent; see Sheet 3 of approved plans for Pima County Permit P18BP05593).

2. Add manufacturer’s literature sheet with dimensional detail for the safety cable guide (Page 22 of 3M DBI-SALA Lad-Saf technical data sheet (Release 1, February 2018) or equivalent).

3. Add manufacturer’s literature sheet with material, grade and dimensional detail for the safety cable (Page 28 of 3M DBI-SALA Lad-Saf technical data sheet (Release 1, February 2018) or equivalent).

4. Add manufacturer’s literature sheet with dimensional detail of the flexible sleeve that attaches to safety cable (Page 18 of 3M DBI-SALA Lad-Saf Technical Data Sheet February 2018) or equivalent).

5. Add “Detail E” illustration on safety cable attachment to lower safety cable mounting bracket

Final Status

Task End Date Reviewer's Name Type of Review Description
05/29/2019 AMARTIN1 OUT TO CUSTOMER Completed