Permit Number - T19BU00161
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2019 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Reqs Change Below are BRC comments on the authorized repair submittal for COT ID# 473 at 2921 North 1st Avenue (T19BU00161).



Sheet 1 of 3



None.



Sheet 2 of 3



1. In 1st & 6th paragraphs of Scope of Work, address any existing and replacement TEK screws or other fasteners that affix Z-clips to metal stringers



2. In 3rd paragraph of Scope of Work, add inches symbol to “3/8” & indicate number of 3/8” carriage bolts per face.



3. In 4th paragraph of Scope of Work, indicate number of new (like) 3/8” carriage bolts per face.



Sheet 3 of 3



1. Add standard Location of Screws Through Z-Clips Into Stringers for each face (see Comment #1 for Sheet 2).
04/26/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/29/2019 AMARTIN1 OUT TO CUSTOMER Completed