Permit Number: T19BU00117
Parcel: 11505161B

Address:
2222 N STONE AV

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T19BU00117
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/26/2019 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Below are comments on the authorized repair submittal for COT ID# 397 at 2224 North Stone Avenue (T19BU00117)

Sheet 1 of 3

1. In aerial photograph underlay site plan, correct the west and south property line dimensions of adjacent Parcel No 115-05-161B (or provide clarifying arrows to indicate the shown dimensions are for the entire lengths of the original lot lines).

2, In Billboard Note #11, revise to indicate that there are no existing light fixtures or electrical service.

Sheet 2 of 3

1. In 2nd paragraph of Scope of Work, clarify that the dimensions of the existing metal trim are the outside dimensions.

2. In 1st paragraph of 1st boxed note below Scope of Work, add ā€œUā€ to account for replacement of structural nuts and bolts.

3. In Poster Panel Side View, add designation for tapered upright indicating existing and to remain.

4. In Title Block, add back Stipulation address in addition to Pima County Addressing address, distinguishing between the two..

Sheet 3 of 3

1. In Detail ā€œAā€ of Side View add designation for tapered upright indicating existing and to remain.

2. In Title Block, add back Stipulation address in addition to Pima County Addressing address, distinguishing between the two..

Final Status

Task End Date Reviewer's Name Type of Review Description
07/12/2019 AVAUGHN1 OUT TO CUSTOMER Completed