Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19BU00101
Parcel: 126134850

Address:
4659 E 22ND ST

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T19BU00101
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2019 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Completed Below are BRC comments on the authorized repair second resubmittal for COT ID# 79 at 4659 East 22nd Street (T19BU00101 R2).

Sheet 1 of 3
None

Sheet 2 of 3
None

Sheet 3 of 3
None

Final Status

Task End Date Reviewer's Name Type of Review Description
08/26/2019 PMARTIN1 OUT TO CUSTOMER Completed