Permit Number: T19BU00101
Parcel: 126134850

Address:
4659 E 22ND ST

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T19BU00101
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2019 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Below are comments on the authorized repair resubmittal for COT ID# 79 at 4659 East 22nd Street (T19BU00101 R).

Sheet 1 of 3
None

Sheet 2 of 3
None

Sheet 3 of 3
1. In Detail B, brace length does not match that indicated in Scope of Work; please resolve this conflict and also add the brace thickness.

2. In Detail B Side View, the revised catwalk width (2’3") does not match the side rail outer width (26 1/2 ") plus the two angle bracket widths (2" each); resolve or otherwise explain this conflict.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/16/2019 QJONES1 APPROVAL SHELF Completed
08/16/2019 QJONES1 OUT TO CUSTOMER Completed
08/16/2019 QJONES1 REJECT SHELF Completed