Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19BU00099
Parcel: 99999999B

Address:
924 E 36TH ST

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T19BU00099
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/10/2019 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Reqs Change Below are BRC comments on the authorized repair submittal for COT ID# 243 at 924 East 36th Street (T19BU00099).



Sheet 1 of 2



None



Sheet 2 of 2



1. In 1st paragraph of Scope of Work, add removal of rigid two-hole straps and 40d pole spikes, including size and number per face.



2. In 8th paragraph of Scope of Work, indicate the size and number of rigid two-hole conduit straps per face and as new (like) and add installation of the new (like) 40d pole spikes, including number per face (consistent with details shown on plan sheet).



3. In boxed Lighting Notes, strike 4th paragraph as being duplicative of 2nd paragraph.



4. In 1st paragraph of 2nd boxed note below Scope of Work, add 2(U) to cover replacement of stringer bolts.



5. In East Face Sign Elevation and Top Stringer Mounting Detail, revise to indicate that the face panels are to be removed and reinstalled.



6. In Poster Panel View and Lighting Arm Mounting Detail, revise to indicate that the light fixtures and light fixture support arms are to be removed and reinstalled.



7. In Light Arm Mounting Detail, delete duplicate reference to the 3x6 wood stringer.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/23/2019 PMARTIN1 OUT TO CUSTOMER Completed