Permit Number: T19BU00073
Parcel: 99999999B

Address:
3623 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T19BU00073
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/18/2019 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Below are comments on the authorized repair submittal for COT ID# 493 at 3623 North Oracle Road (T19BU00073).

Sheet 1 of 4

None

Sheet 2 of 4

1. In 4th & 5th paragraphs of Scope of Work, specify the number of existing and replacement carriage bolts per face.

2. In 8th paragraph of Scope of Work, clarify if ladder dimensions and material grade are like or not (see Comment #1 for Sheet 4 of 4), and if not provide OSHA mandate requiring change.

3. Add side view or other appropriate depiction of billboard structure showing location of upper access ladder and specifying the vertical dimension from grade to lower internal catwalk and from lower internal catwalk to upper internal catwalk at respective points where upper access ladder is attached to catwalks.

Sheet 3 of 4

1. Add standard Stringer Mounting Detail.

Sheet 4 of 4

1. Add detail showing diameter of rungs and width and thickness of ladder side rails, indicating whether existing and replacement are like.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/26/2019 PMARTIN1 OUT TO CUSTOMER Completed