Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19BU00017
Parcel: 99999999S

Address:
5085 E 29TH ST

Review Status: Active

Review Details: BILLBOARD - BLDG30days

Permit Number - T19BU00017
Review Name: BILLBOARD - BLDG30days
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2019 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Below are comments on the authorized electrical repair second resubmittal for COT ID# 318 at 5085 East 29th Street (T19BU00017 R2).

Sheet 1 of 2

None

Sheet 2 of 2
1. In 3rd, 4th & 13th paragraphs of Scope of Work, correct the number of conductors; Comment #5 on the 1st resubmittal (6/20/19) was not responded to in this regard.
2. In 9th paragraph of Scope of Work, delete phrase “at TEP pole and” and change “risers” to singular, as the phrase is now duplicative of language in added 8th paragraph of Scope of Work above.
3. Add note in appropriate location of plan sheet reflecting engineer’s response to Comment #1 that 2nd breaker that comes with 122PROG to be removed and replaced with space cover.
4. Add note clarifying that terminals #5 & #6 and any associated wiring depicted in the wiring diagram for the Tork EWZ103 shown are not used.
5. In Panel Schedule, cross out circuits shown as #5 & #7 as the 122 panel does not provide for these spaces.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/12/2019 ANY REJECT SHELF RECEIVED