Permit Number: T18RW05269
Parcel: 999999999

Address:
236 W WETMORE RD

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T18RW05269
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2019 JSANDER1 DOT_ELEC REVIEW Approved Shot Clock approval.
01/04/2019 JSANDER1 REAL_ESTATE REVIEW Approved COT License#: LF983
11/30/2018 LINZUNZA START START Completed
11/30/2018 LINZUNZA WATER REVIEW Approved
11/30/2018 LINZUNZA HISTORIC Review Approved
12/04/2018 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change Reviewr : Richard Leigh 520-837-6647
Richard.Leigh@tucsonaz.gov

1. Revise drawing to depict sight distance triangle per COT Technical Standards Manual Sec. 10-01.5.0. The proposed meter pedestal must be located outside of the site visibility triangle.

2. Submit temporary traffic control plan for review.
12/06/2018 LINZUNZA IT_NETWK REVIEW Approved
12/06/2018 LINZUNZA DOT STREET MAINTENANCE REVIEW Approved