Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/17/2018 | JSANDER1 | START | START | Completed | |
09/17/2018 | JSANDER1 | DOT_ELEC | REVIEW | Reqs Change | Sheet A-5: remove reference to "10 amp KTK Fuse" in drawing text next to hand hole. Fuses SHALL BE Cooper Bussman LP-CC-5. Note 1: Edit to state "most" residential roadway lighting systems have been converted from single phase 240 volt/480 volt systems to one line of 240 volt and Neutral line. (To save time in the future, although this particular install is single phase 480-volt) Also on A-5 fuse holders are to be Cooper-Bussman HEB-AA type no substitutions. Provide a reference to installation of 25 FT coil of #4 AWG solid Cu wire to be installed in the foundation with enough slack to tie in to either ground buss in pole or grounding lug at hand hole near base. |
09/17/2018 | JSANDER1 | HISTORIC | Review | Approved | Special Exception #: SE-17-135 |
09/17/2018 | JSANDER1 | WATER | REVIEW | Approved | No conflict letter issued September 10, 2018 by Tom Cantrell from Tucson Water. |
09/20/2018 | RICHARD LEIGH | DOT ENGINEERING | REVIEW | Approved | |
09/20/2018 | LINZUNZA | IT_NETWK | REVIEW | Approved | |
09/26/2018 | JSANDER1 | DOT STREET MAINTENANCE | REVIEW | Approved | |
09/26/2018 | JSANDER1 | REAL_ESTATE | REVIEW | Needs Review |