Review Details: ROW SWF - SUBMITTAL

Permit Number - T18RW03925
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2018 JSANDER1 START START Completed
08/31/2018 JSANDER1 DOT_ELEC REVIEW Approved Pole Type as APPROVED T18RW02823
08/31/2018 JSANDER1 DOT STREET MAINTENANCE REVIEW Reqs Change Pole Type as APPROVED T18RW02823
New pole location is not approved. Please submit revised plans showing either:
a) new pole replacing existing pole at location of existing pole
b) new pole location to be previously authorized via written approval from Traffic Maintenance
08/31/2018 JSANDER1 WATER REVIEW Passed not needed
08/31/2018 JSANDER1 HISTORIC Review Approved 3/15/18 Historic Approval Letter
09/11/2018 JSANDER1 REAL_ESTATE REVIEW Needs Review
09/12/2018 CSALTZM1 DOT ENGINEERING REVIEW Denied 1) Sheet A-1 , Note 12 - "New street light pole to be replace existing street light pole"
ADD the following to the note: New light pole to be located at the same location as the existing pole.
2) Change all drawing and notes to reflect new location.
3) Sheet A-1 Note 14 "New AT&T meter pedestal w/I.L.C. on new 22"x22"x4" pre -cast concrete pad. Move location of meter pedestal north to a location where the pedestal has a minimum distance between the sidewalk and the pedestal of one 0foot.
4) Change all drawing and notes to reflect new location.
09/26/2018 JSANDER1 IT_NETWK REVIEW Needs Review