Permit Review Detail
Review Status: Completed
Review Details: ROW SWF - RE-SUBMITTAL
Permit Number - T18RW03697
Review Name: ROW SWF - RE-SUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/17/2018 | JSANDER1 | START | START | Completed | |
10/22/2018 | JSANDER1 | DOT_ELEC | REVIEW | Reqs Change | Still an issue of the fuse holder. 1: A-2 key notes #15 1 1/2 conduit depth should be 30''s same change should be made on E-2 key notes #14. 2: A-3 key notes #6 calls for 2' x 9' foundation doesn't show rebar cage, plus why is it a smaller size than the foundations we are installing now they are 2' 6" by 11' 0" ? 3: E-2 key note #3 we should note if pull box is damaged it shall be replaced with a new pull box. 4: E-2 key notes #10 same as A-3 Key note #6. |
10/24/2018 | JSANDER1 | REAL_ESTATE | REVIEW | Approved | COT License #: LF977 |