Plan Number: T18PI00039
Parcel: Unknown

Address:
5975 S TUCSON BL

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T18PI00039
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2019 GARY WITTWER DOT LANDSCAPE REVIEW Approved
01/24/2019 ZELIN CANCHOLA DOT TRAFFIC REVIEW Reqs Change January 24, 2019
Activity Number - T18PI00039
Project Name - Tres Pueblos Este
Projecr Reviewer - Zelin Canchola

RESUBMITTAL REQUIRED: DOT Review Section has reviewed the PIA Plan for Traffic Engineering. Resubmit with the following

1. Add - Show quantities of new traffic signs.

2. Show on plan required signs, including Stop signs (none required at T-intersections) street name signs, and no parking fire access signs within cul-de-sacs.

If you have any questions I can be reached at 837-6659 or zelin.canchola@tucsonaz.gov
01/25/2019 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved
01/28/2019 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change January 28, 2019
SUBJECT: Paving Plans Tres Pueblos Este T18PI00039, I-2018-023
PROJECT REVIEWER: Richard Leigh, TDOT, TDOT Eng. Review
RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to resubmittal. Please include a response letter addressing the following comments and return redlined drawings with subsequent submittal.
1. Include the plan number “I-2018-023” in the title block of each sheet.
2. Include the PIA activity number “T18PI00039” on cover sheet.
3. Sheets 2 through 9: Remove signatory titles from title blocks.
4. Sheet 1, General Paving Note 8: Revise note to indicate the use of TDOT Mix No. 2 for the asphaltic concrete.
5. Sheet 2 & 8: Call out standard detail for new to existing curb and sidewalk connections at Tucson Blvd. and Bilby Rd.
6. Call out all proposed curb access ramps and indicate type.
7. Call out all proposed sidewalk scuppers.
8. Provide all details in this plan set for all proposed storm drain crossings proposed in the public right-of-way. Private drainage easement will need to be obtained for the private storm drains in the ROW.
9. Sheet 9, Section A: Per TSM 2-01.9.0 a minimum 2’ setback is required from top/toe of slope and property line.
10. Please Refer to redline plans for additional comments and comment details.
If you have any questions, I can be reached at 837-6647 or emailed at Richard.Leigh@tucsonaz.gov.
02/28/2019 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Reqs Change
03/08/2019 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed Please submit utility notification confirmation for the utility companies listed on the PIA utility notification list. The list can be found at: https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Jan14z.pdf
03/08/2019 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Reqs Change
03/08/2019 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed Please submit utility notification confirmation for the utility companies listed on the PIA utility notification list. The list can be found at: https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Jan14z.pdf
03/08/2019 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Reqs Change
03/08/2019 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Reqs Change
03/08/2019 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Reqs Change
03/08/2019 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Reqs Change
03/08/2019 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Reqs Change
03/08/2019 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Reqs Change
03/08/2019 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Reqs Change