Plan Number: T18PI00036
Parcel: Unknown

Address:
635 W ROGER RD

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T18PI00036
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2018 GARY WITTWER DOT LANDSCAPE REVIEW Approved No planting or irrigation in ROW
12/10/2018 LPETERS2 DOT PERMITS & CODES REVIEW Approved
12/10/2018 ZELIN CANCHOLA DOT TRAFFIC REVIEW Completed Em ZC to DOT no comments.fbs
12/10/2018 FSHENK1 UTILITY CLEARANCES COT STREETS DIVISION Completed
12/10/2018 FSHENK1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
12/10/2018 FSHENK1 UTILITY CLEARANCES PC WASTEWATER MGMT Completed
12/10/2018 FSHENK1 UTILITY CLEARANCES QUEST COMMUNICATION Completed
12/10/2018 FSHENK1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
12/10/2018 FSHENK1 UTILITY CLEARANCES COX COMMUNICATION Completed
12/10/2018 FSHENK1 UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
12/10/2018 FSHENK1 UTILITY CLEARANCES EL PASO NATURAL GAS Completed
12/10/2018 FSHENK1 UTILITY CLEARANCES KINDER MORGAN ENERGY Completed
12/20/2018 JIM FEMLING DOT STREET MAINTENANCE REVIEW Completed 12/20/2018 - per email JFemling to DOT; No comments
12/20/2018 FSHENK1 PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
12/20/2018 FSHENK1 PIA COORDINATOR OUT TO CUSTOMER Completed
12/21/2018 RICHARD LEIGH DOT ENGINEERING REVIEW Approved December 3, 2018

SUBJECT: HSSA Animal Welfare Center - 635 West Roger Road, U-2018-013, T18PI00036

PROJECT REVIEWER: Richard Leigh, TDOT Engineering Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and recommends a tentative approval at this time. The following comments need to be addressed prior to submitting mylars for signature.

1. Sheet 1: Include the plan number "U-2018-013" in the title block of each sheet.

2. Sheet 1: Include the PIA activity number "T18PI00036" on cover sheet.

3. Sheet 2: A public access easement is required when public sidewalk and curb access ramps encroach onto private property. Delineate and label with recordation information any required easements.

4. Sheet 2: Remove signatory titles from title block.

5. Sheet 2: Revise sidewalk scupper details to indicate that the sidewalk scupper will extend a minimum of 1 foot beyond the sidewalk on both sides of the scupper.

6. Please Refer to redline drawings for additional comments and comment details.

7. Please email a PDF copy of revised drawing for curtesy review prior to submitting mylars for signature.

If you have any questions, I can be reached at 837-6647 or emailed at Richard.Leigh@tucsonaz.gov.