Plan Review Detail
Review Status: Completed
Review Details: PIA - RESUBMITTAL
Plan Number - T18PI00019
Review Name: PIA - RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/09/2018 | FSHENK1 | UTILITY CLEARANCES | PC WASTEWATER MGMT | Completed | |
| 11/09/2018 | FSHENK1 | UTILITY CLEARANCES | QUEST COMMUNICATION | Completed | |
| 11/09/2018 | FSHENK1 | UTILITY CLEARANCES | COX COMMUNICATION | Completed | |
| 11/09/2018 | FSHENK1 | UTILITY CLEARANCES | SOUTHWEST GAS CORP | Completed | |
| 11/09/2018 | FSHENK1 | UTILITY CLEARANCES | EL PASO NATURAL GAS | Completed | |
| 11/09/2018 | FSHENK1 | UTILITY CLEARANCES | KINDER MORGAN ENERGY | Completed | |
| 12/10/2018 | FSHENK1 | UTILITY CLEARANCES | COT STREETS DIVISION | Completed | |
| 12/10/2018 | FSHENK1 | UTILITY CLEARANCES | COT WATER NEW DEVELOPMENT | Completed | |
| 12/18/2018 | FSHENK1 | PIA COORDINATOR | CUSTOMER CALLED; PLANS @ AMBASSADOR | Completed | |
| 12/18/2018 | CSALTZM1 | DOT ENGINEERING | REVIEW | Denied | 1. Need details of access ramps showing grades. Also need to show the slope between the two access ramps on Bell Rock Trail and Houghton Road. 2. Need easement for headwall and pipes which are shown to be located outside of the right of way of Houghton Road at Bell Rock Trail. 3. Remove 6" vertical curb and replace with 8" PAG Std. 209 Type 2 Curb. 4. Replace pavement section with the following as-built pavement section used on Houghton Road. 2"ARAC 2.5"C.O.T. Mix #1 12" ABC |
| 12/18/2018 | FSHENK1 | PIA COORDINATOR | OUT TO CUSTOMER | Completed | |
| 12/18/2018 | FSHENK1 | UTILITY CLEARANCES | TUCSON ELECTRIC POWER CO | Completed |