Plan Number: T18PI00019
Parcel: Unknown

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T18PI00019
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2018 ZELIN CANCHOLA DOT TRAFFIC REVIEW Approved
09/24/2018 CSALTZM1 DOT ENGINEERING REVIEW Denied 1) Add PIA No.T18PI00019 to Cover sheet top center
2) Add Plan No. U-2018-008 to all sheets in title block.
3) Sheet 3 of 4 need pavement structural section
4) Sheet 3 of 4 Channel Section need dimension to right top of bank.
5) Sheet 3 of 4 indicate channel section on plan view.
6) Sheet 3 of 4 "Paving note 4" - Show all improvement in the Right of Way on this plan.
7) Sheet 3 of 4 Provide details for pipe culvert in the Right of Way.
8) Sheet 3 of 4 Provide raised median islands with PAG Type 2 std. curb.
09/25/2018 TWOLFGA1 PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
09/25/2018 JIM FEMLING DOT STREET MAINTENANCE REVIEW Completed
09/25/2018 TWOLFGA1 PIA COORDINATOR OUT TO CUSTOMER Completed
09/25/2018 TWOLFGA1 UTILITY CLEARANCES COT STREETS DIVISION Approv-Cond
09/25/2018 TWOLFGA1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied
09/25/2018 TWOLFGA1 UTILITY CLEARANCES PC WASTEWATER MGMT Denied
09/25/2018 TWOLFGA1 UTILITY CLEARANCES QUEST COMMUNICATION Denied
09/25/2018 TWOLFGA1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied
09/25/2018 TWOLFGA1 UTILITY CLEARANCES COX COMMUNICATION Denied
09/25/2018 TWOLFGA1 UTILITY CLEARANCES SOUTHWEST GAS CORP Denied
09/25/2018 TWOLFGA1 UTILITY CLEARANCES EL PASO NATURAL GAS Denied
09/25/2018 TWOLFGA1 UTILITY CLEARANCES KINDER MORGAN ENERGY Denied