Plan Number: T18PI00013
Parcel: Unknown

Address:
4975 E BENSON HY

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T18PI00013
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2018 ZELIN CANCHOLA DOT TRAFFIC REVIEW Denied April 30, 2018


SUBJECT: Valencia Crossing
PIA Plan T13PI00016

PROJECT REVIEWER: Zelin Canchola,
DOT Review Section

RESUBMITTAL REQUIRED: DOT Review Section has reviewed the PIA Plan for Traffic Engineering. Resubmit with the following

1. List quantities and descriptions for striping materials including number and type of RPM's, lineal footage quantities of longitudinal and traverse striping arrows, words and symbols.

2. Show marking details and symbol legends according to pavement marking standards.

If you have any questions I can be reached at 837-6659 or zelin.canchola@tucsonaz.gov
05/10/2018 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change May 10, 2018


SUBJECT: Interim Roadway Improvements Plans for Valencia Crossing Infrastructure

PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval at this time. The following comments need to be addressed prior to in the subsequent review submittal. Please return redlined drawings with next submittal.

1. Include the plan number "I-2018-008" in the title block of each sheet.

2. Remove PIA activity number "T13PI00016"on cover sheet and replace with"T18PI00013.

3. Revise plan tile to include the word interim.

4. Sheet 2: Provide complete details for the proposed storm drain located at +/-70+00 (Valencia Crossing Dr). Include inlet and outlet structures, inverts and class of pipe. Also, provide a section of it.

5. Sheet 2: Provide details for the rock rip-rap pad at the north end of Valencia Crossing Dr.

6. Sheet 2 & 3: indicate the final surface treatment and preparation requirements for the section of the roadway that will graded and not paved.

7. Provide a section showing the future roadway section and reference plan number I-2013-017

8. Submit a drainage report/statement and hydraulic analysis supporting the interim roadway infrastructure.

9. Provide a pedestrian circulation path pursuant to T.S.M. 7-01.3.3.a along Valencia Crossing Dr to Valencia Rd or pursue relief from requirement via a TSMR.

Please Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsonaz.gov
06/01/2018 LPETERS2 DOT PERMITS & CODES REVIEW Denied I have reviewed this plan and have the following comment:

Sheet 1 - Note 5 - This note should state," Asphalt concrete shall conform to City of Tucson Mix #2".

No further comments.

Lance Peterson, P.E.
520-837-6777
06/11/2018 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved APPROVED - DUE TO NO RESPONSE AFTER NUMEROUS REQUESTS.
06/11/2018 LINZUNZA PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
06/11/2018 LINZUNZA PIA COORDINATOR OUT TO CUSTOMER Completed
12/12/2018 TWOLFGA1 DOT ENGINEERING ADMINISTRATOR REVIEW Completed