Plan Number: T18PI00001
Parcel: Unknown

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T18PI00001
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2018 LPETERS2 DOT ENGINEERING REVIEW Reqs Change SUBJECT: La Estancia De Tucson Phase 2 Public Paving and Drainage Improvements

PROJECT REVIEWER: Richard Leigh, TDOT Engineering Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to final approval. Please include a response letter addressing the following comments and return any redlined drawings with subsequent submittal.

1. Sheet 1: Include the plan number "I-2018-001" in the title block of each sheet.

2. Sheet 1: Include the PIA activity number "T18PI00001" on cover sheet.

3. Sheet 2, Revise Paving Note 5 to indicate City of Tucson "City Mix" asphalt Mix #2.

4. Sheet 2 Paving note 15: Revise phone number for Paul Rosenboom to 520-791-3154 .

5. Sheet 3 Detail A: Revise detail to reference placement of curb access ramps per PAG Standard Detail 207, Type 1.

6. Sheet 4 - 8: Indicate placement of survey monuments per PAG Standard Detail 103 at roadway intersections and at the points of curvature along roadway center line

7. Please Refer to redline drawings for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or emailed at Richard.Leigh@tucsonaz.gov.
01/09/2018 LPETERS2 DOT PERMITS & CODES REVIEW Denied I have reviewed these plans and have the following comments:

1. Sheet 2, Paving Note 5 - This should state : "Asphalt Concrete shall conform to City of Tucson Mix#2."
2. Sheet 3 - Curb Ramp Detail - Please reference the PAG 2015 Detail and ramp type.

No further comments.

Lance Peterson, P.E.
(520) 837-6777
02/01/2018 ZELIN CANCHOLA DOT TRAFFIC REVIEW Reqs Change February 1, 2018


SUBJECT: La Estancia Phase 2 T18PI00001 (I-2008-001)


PROJECT REVIEWER: Zelin Canchola,
TDOT Review Section

RESUBMITTAL REQUIRED: DOT Review Section has reviewed the PIA Plan for Traffic Engineering. The proposed plan requires the following change:

1. Add - Street name signs
2. Add - Stop signs
3. Add - No Parking fire access signs


If you have any questions I can be reached at 837-6659 or zelin.canchola@tucsonaz.gov
02/13/2018 LINZUNZA UTILITY CLEARANCES COT STREETS DIVISION Denied
02/13/2018 GARY WITTWER DOT LANDSCAPE REVIEW Passed
02/13/2018 LINZUNZA UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied
02/13/2018 LINZUNZA UTILITY CLEARANCES PC WASTEWATER MGMT Denied
02/13/2018 LINZUNZA UTILITY CLEARANCES QUEST COMMUNICATION Denied
02/13/2018 LINZUNZA UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied
02/13/2018 LINZUNZA UTILITY CLEARANCES COX COMMUNICATION Denied
02/13/2018 LINZUNZA UTILITY CLEARANCES SOUTHWEST GAS CORP Denied
02/13/2018 LINZUNZA UTILITY CLEARANCES EL PASO NATURAL GAS Denied
02/13/2018 LINZUNZA UTILITY CLEARANCES KINDER MORGAN ENERGY Denied
02/23/2018 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved
02/23/2018 LINZUNZA PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
02/23/2018 LINZUNZA PIA COORDINATOR OUT TO CUSTOMER Completed