Permit Number: T18OT01276
Parcel: 112040340

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T18OT01276
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2019 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. The elevation certificate provided with the permit application show two lowest floor elevations. Show the floor elevations for all existing floors that will remain.
2. Since the addition is a substantial improvement, show the minimum floor elevation (2407.1 NAVD88) on all new floors. For both of these conditions the elevation should be on the floor plans.
3. Show the whole extent of the French drain. The drain must extend past the carport, per the DDO decision letter. Clearly show the proposed outlet location on the site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/18/2019 KROBLES1 OUT TO CUSTOMER Completed