Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T18CM10091
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/05/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/05/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide plans sealed by an Arizona Registrant. Ref; ARS 32-125, Board of Technical Registration Rules R4-30-304. |
06/03/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Correct the notes on sheets M2.2, M2.3, and M2.4 that call for the 10" x 10" exhaust duct near column F-3 to run up to the roof. |
06/03/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide separate indirect waste pipes for each compartment of the 3-compartment sink in Food Prep, 007, to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.1, IPC 2018 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/03/2020 | JGARCIA1 | APPROVAL SHELF | Reqs Change |
06/03/2020 | JGARCIA1 | OUT TO CUSTOMER | Completed |
06/03/2020 | JGARCIA1 | REJECT SHELF | Completed |