Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T18CM10083
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/26/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/28/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Show how the supply and drain piping in the restroom has been modified for Revision 2. Reference: Section 107.2.1, IBC 2018. |
08/03/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response. 1. Provide a complete electrical line diagram including load calculations. 2. Provide a complete panel schedule and identify the new 200 amp panel on the 2nd electrical floor plan. 3. Provide GFI protected receptacles for the drinking fountain and the restroom and kitchen where applicable. NEC 210.8, 422.5. 4. Revise the NEC reference in the electrical notes to the current 2017 NEC. 5. Indicate what IBC code section applies to electrical notes #13, #14, #17, #18. 6. Provide a complete luminaire schedule. 7. Provide compliance with the 2018 IECC for the lighting. 8. Indicate what electrical devices and luminaires are new and or existing on the 2nd floor electrical plan 9. The Registrant Seal is expired. Ref; 2018 IBC sec. 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/04/2021 | VVERA1 | OUT TO CUSTOMER | Completed |