Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM10083
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/03/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/03/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
01/03/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | ELECTRICAL PLAN REVIEW COMMENTS T18cm10083 Please address the following electrical plan review comments. Also provide a written response. #1. Please provide a complete line diagram of the power distribution equipment. Show the OCPD protecting the feeder and new panel, conduit conductor sizes and types. Include load calcs. REF; 2017 NEC, 2018 IBC sec 107.2.1 |
01/03/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/03/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/03/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
12/31/2018 | MCASTRO2 | ENGINEERING | REVIEW | Passed | |
12/31/2018 | MCASTRO2 | ZONING | REVIEW | Approved | |
12/31/2018 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/08/2019 | QJONES1 | APPROVAL SHELF | Completed |
01/08/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
01/08/2019 | QJONES1 | REJECT SHELF | Completed |