Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Please provide plans sealed by Professional Engineers, Architects registered in the State of Arizona for all Plan Sheets submitted. Electrical and Structural.
2. Indicate or show the location of the Rapid Shutdown Switch. Also provide labeling with wording for the PV system as indicated in NEC art; 690.12C and 690.56C,1 thru 6.
3. Ref; Plan Sheet E-602.01. Placard 3, Label 2, are not legible. The background is to dark to make out the wording of the labels.
4. The manufacturer spec sheet did not indicate ground fault protection for the DC source circuits. Please verify.
Ref; 2018 IBC sec 107.2.1, 2017 NEC art 690, City of Tucson Commercial Plan Submittal Requirements. www.tucsonaz.gov/pdsd.
Dan Santa Cruz
Commercial Electrical Plan Review, City of Tucson