Permit Number: T18CM10058
Parcel: 12009309D

Address:
4775 S 3RD AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM10058
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2019 MARTIN BROWN FIRE REVIEW Approved
02/04/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 2; Note 17: This note indicates a 24" wide x 6" deep thickened slab at the masonry wall. The slab (per Note 17) is 6" thick. Please provide a detail for Note 17, or indicate on Section 1/4 to clarify.
2. Sheet 2; Note 21: Please provide a detail for this pvc wall drain.
3. Sheet 2; Note 22: Please reference Building Section A/3 in this note.
4. Sheet 2; Floor Plan: The Sections A and B should reference Sheet 3. Please revise.
5. Sheet 3 (Section "B"); Sheet 4 (Section 1): Please indicate on Section 1 the thickened slab at the interior block wall as shown on Section "B".
6. Sheet 4; Section 1: The wall vertical reinforcing is indicated at 18" o.c. This doesn't fit with block wall cores. Should this spacing be revised?
7. General: Please provide the Special Inspection Certificate for caissons with Parts A and B completed.
8. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911

Final Status

Task End Date Reviewer's Name Type of Review Description
02/08/2019 QJONES1 APPROVAL SHELF Completed
02/08/2019 QJONES1 OUT TO CUSTOMER Completed
02/08/2019 QJONES1 REJECT SHELF Completed