Permit Number: T18CM10048
Parcel: 117090260

Address:
1021 S 6TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM10048
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2019 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/07/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
01/07/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a complete one line diagram as outlined per the City Of Tucson Commercial Plan Submittal Requirements for electrical plan submittal. These requirements can be printed or downloaded from www.tucsonaz.gov/pdsd. Also be advised that if the electrical designs exceeding 400 amps or 22,000 AIC, it will require an Electrical Engineer registered in the state of Arizona to design and seal the electrical plans.
#2. Provide the following information;
(a) Voltage, Phase, Amp, AIC ratings and load calcs of the service and all associated equipment.
(b) Verify the existing electrical service is fed overhead by the utility. Otherwise, the new service must be fed underground by the serving utility.
(c) Assign branch circuits and panel numbers for the devices and luminaires.
Ref; 2012 IBC sec 107.2.1 and amendments, 2011 NEC, City Of Tucson Commercial Plan Submittal Requirements for electrical plan submittal. Arizona Revised Statutes.
01/07/2019 GPERU1 FIRE REVIEW Needs Review
01/07/2019 GPERU1 BUILDING-COMMERCIAL REVIEW Needs Review
01/07/2019 ROBERT SHERRY WATER REVIEW Completed
01/07/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
01/08/2019 MCASTRO2 ENGINEERING REVIEW Needs Review
01/08/2019 MCASTRO2 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/22/2019 AMARTIN1 APPROVAL SHELF Completed