Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM10041
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/16/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/16/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size used on the drawings to a minimum height of 3/32-inch (see sheets M1.1, M1.2 and M1.3). Reference: Section 107.2.1, IBC 2018. 2. Provide heating and cooling load calculations to justify the selection of the roof top units. Reference: Sections C403.1.1 and C403.3.1, IECC 2018. 3. Condensate drains shall be terminated at an approved disposal location. A splash block on the roof is not an approved location. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson. 4. Clarify the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Coordinate with the electrical design. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018. |
| 01/16/2019 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Some confusion on cover sheet. Life safety summary indicates no alarm system required by code but code data lists fire alarm system modifications will be a deferred submittal. Please clarify. Be advised, duct smoke detectors need to report as a supervisory signal to a constantly attended location. |
| 01/16/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the specified metering faucets for the restrooms will dispense a maximum of 0.25 gallons per metering cycle and that the metering cycle will operate for a minimum time of 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. |
| 01/18/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/18/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/29/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; plan Sheet E2.0, E2.1. Indicate new and existing equipment on the line diagrams and panel schedules. 2. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code (OLC). 3. See section 104 for plan submittal requirements. Do not confuse the Outdoor Lighting Code with the IECC for exterior lighting. The Outdoor Lighting Code can be downloaded from www.tucsonaz.gov/pdsd. Ref; 2012 IBC sec 107.2.1, 2011 NEC |
| 01/30/2019 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 01/30/2019 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: Harbor Freight Tools - 3739 N Oracle Rd T18CM10041 Building Plan (1st Review) TRANSMITTAL DATE: January 30, 2019 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Provide a dimension from the southeast corner of the proposed cart corral to the building column located to the southeast. A minimum 4'-0" clear sidewalk must be maintained. 3. Provide a parking space depth dimension for the proposed accessible vehicle parking spaces. 4. Until all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/13/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 02/13/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 02/13/2019 | QJONES1 | REJECT SHELF | Completed |