Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM10039
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/03/2019 | AMARTIN1 | ZONING | REVIEW | Reqs Change | |
01/03/2019 | AMARTIN1 | ENGINEERING | REVIEW | Needs Review | |
01/03/2019 | MASHFOR1 | FIRE | REVIEW | Approved | |
12/28/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/28/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide heating/cooling load calculations for the proposed heat pump. |
12/28/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please provide written responses to all plan review comments. 1. The architectural sheets must be sealed by a professional registrant; sheets are not sealed. 2. A drinking fountain(s) are required for standing and persons in wheelchairs. Show location along the accessible route. IBC TABLE 2902.1. 3. Identify the door? in the demising wall and indicate the occupancy of the suite that it opens into. IBC 107.2.1. 4 Provide a life safety exiting plan for the entire suite. IBC 107.2.1. |
12/28/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
12/28/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Coordinate the power requirements for the new water heater with the electrical engineer. |
12/28/2018 | GPERU1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |