Permit Number: T18CM10039
Parcel: 135074550

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM10039
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2019 AMARTIN1 ZONING REVIEW Reqs Change
01/03/2019 AMARTIN1 ENGINEERING REVIEW Needs Review
01/03/2019 MASHFOR1 FIRE REVIEW Approved
12/28/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/28/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating/cooling load calculations for the proposed heat pump.
12/28/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change Please provide written responses to all plan review comments.
1. The architectural sheets must be sealed by a professional registrant; sheets are not sealed.
2. A drinking fountain(s) are required for standing and persons in wheelchairs. Show location along the accessible route. IBC TABLE 2902.1.
3. Identify the door? in the demising wall and indicate the occupancy of the suite that it opens into. IBC 107.2.1.
4 Provide a life safety exiting plan for the entire suite. IBC 107.2.1.
12/28/2018 ROBERT SHERRY WATER REVIEW Completed
12/28/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Coordinate the power requirements for the new water heater with the electrical engineer.
12/28/2018 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed